The provided information outlines part number options and general installation and operating notes for the equipment specified. Here's a breakdown of the details:
Part Number Options:
8200-1300: LVDC (18–32 Vdc) Standard Compliance
8200-1301: AC/DC (88–132 Vac or 90–150 Vdc) Standard Compliance
8200-1302: Marine/ATEX Compliance LVDC (18–32 Vdc)
General Installation and Operating Notes and Warnings:
The equipment is suitable for use in:
Class I, Division 2, Groups A, B, C, and D (Class I, Zone 2, Group IIC) hazardous locations.
European Zone 2, Group II environments per compliance with EN60079-15, Electrical apparatus for explosive atmospheres – Type of protection ‘n’.
Field wiring must use stranded copper wire rated at least 75°C for operating ambient temperatures expected to exceed 50°C.
Peripheral equipment must be suitable for the location where it's used.
Wiring must follow North American Class I, Division 2, or European Zone 2 wiring methods as applicable and comply with the authority having jurisdiction.
For the Marine Type approved version, field wiring must include an additional shield layer grounded to the enclosure. This additional shielding goes beyond standard shielding and may be solid or flexible metal conduit, armored cabling, or a cable with an overall shield.
These guidelines ensure proper installation, operation, and compliance with safety standards for the specified equipment in hazardous or non-hazardous environments.