APPLICATION:
Under effect of heat and electric field, the exposure of insulation oil not only contained trace water, gas, particulate matters, but also acid, sludge, pitches and dissociated carbon. ASSEN ZYD-I Double Stage High Vacuum Transformer Oil Regeneration System machine can fast remove the moisture, gas and mechanical impurities as well as eliminating organic acid, sludge, pitches and dissociated carbon in the deteriorated transformer oil which are difficult to be removed by conventional oil purifier plants. After the treatment, the regenerated oil can met the required standard and life span of new insulation oil.
FEATURES:
1.Double-stage
vacuum system, strong power of vacuum evacuating, ultimate vacuum
value ≤ 5Pa
2.Two
vacuum separating chambers, efficient oil film sprayer,
increasing separating size and separating time to ensure the
dry-level and dielectric strength improving
greatly.
3.Double-horizontal
film evaporation technology, combined with unique and advanced
dewatering, degassing components, can rapidly and effectively
separate water, gas from oil.
4.Multi-stage
precision filtration system, mesh filtration combined with
molecular adsorption technologies.
5.Efficient
electric heating system, heating uniformity, less power
consumption, safe, and reliable.
6.Double-infrared
liquid level sensor, pressure protective system to ensure machine
operation easy and safely.
7.Adopt
interlocked protective system, which connect oil pump, heater and
liquid level sensor, avoiding blank heating, blank pumping, oil
leak and electricity leak. If there is any fault, machine will be
power off automatically.
8.Functions
of live line work onsite, vacuum drying and vacuum oiling.
9. Filter medium can fast and effectively remove acid, free carbon
ADVANTAGE:
1.It can treat deteriorated transformer oil.2.It can significantly improve oil color. Dark-colored oil can be retrofitted to the color less than 1.5.3.It can recover aging insulating oil electrical with PH value ≥5.5, acid value ≤0.03 mg koH/g, or dielectric loss factors tgδ (90℃) ≤0.001 back to new oil characteristics.4.Economical. Extremely dirty oil can be reused after regeneration. The cost of purchasing regenerated oil is typically less than 90% of new oil.5.Control of strategic asset is retained. Oil in use is an asset. Use of regeneration technology removes dependence of the oil company on replacement suppliers and isolates them from wildly fluctuating external market prices.6.Extended life of power transformer equipment.
Technical Specifications:
Parameters |
Unit |
ZYD-I-30 |
ZYD-I-50 |
ZYD-I-100 |
ZYD-I-150 |
ZYD-I-200 |
ZYD-I-250 |
ZYD-I-300 |
|
Flow rate |
L/min |
30 |
50 |
100 |
150 |
200 |
250 |
300 |
|
Working vacuum |
Mpa |
-0.095 ~ -0.099 |
|||||||
Working Pressure |
Mpa |
≤0.5 |
|||||||
Temperature Range |
℃ |
20 ~ 80 |
|||||||
Power supply |
Three Phase 50HZ 380V |
||||||||
Working hours without trouble |
Hr |
≥4000h |
|||||||
Continuous working hours |
Hr |
≥720h |
|||||||
Working Noise |
Db(A) |
75 |
75 |
75 |
80 |
80 |
80 |
80 |
|
Heating Power |
KW |
30 |
36 |
45 |
60 |
75 |
90 |
120 |
|
Total Power |
KW |
35.5 |
41 |
52.5 |
71.4 |
86.5 |
102.5 |
135 |
|
Inlet/Outlet |
mm |
φ25 |
φ32 |
φ42 |
φ50 |
φ50 |
φ60 |
φ60 |
|
Weight |
Kg |
420 |
500 |
650 |
950 |
1100 |
1500 |
1850 |
|
Overall |
Length |
mm |
1350 |
1480 |
1890 |
2150 |
2300 |
2550 |
2770 |
Width |
mm |
1050 |
1150 |
1550 |
1750 |
1850 |
2050 |
2200 |
|
Height |
mm |
1300 |
1450 |
1850 |
1950 |
2100 |
2400 |
2700 |