Port | Shanghai,tianjin,weihai,shenzhen,beijing |
Packaging | 1Pc/Box |
Lead Time | 35-60days |
FUJI FKP
Direct mounted Pressure transmitter(DC4~20mA+HART protocol)
FUJI FDP Direct mounted Pressure transmitter(FOUNDA TION Fieldbus
protocol or PROFIBUS-PA)
1.Product Introduce
Fuji
FCX -AIII version
FKP/FDP directly installed pressure transmitter, which is
designed for the pipeline to be install directly. There are many
process connection selection available, accurately measured,
online adjustment, and convenient operation.
The FKP/FDP pressure transmitter accurately measures pressure and
converts it into an output signal of 4~20mA DC.The transmitter
utilizes a unique micromachined capacitance silicon sensor with
advanced floating capsule structure and newer micro-processing
technology, the transmitter has high accuracy, good stability,
safety and reliability, and easy to use.
2:Products Features
1. High accuracy
Pressure transmitter can be carried out with high accuracy
measurement in the range of 8.125-50000kPa.
Standard accuracy: ± 0.065%
High accuracy(optional):± 0.05%
2. Excellent operability and easy to use
It has an excellent operability and easy to use in any
application.
All range meet the requirements of explosion-proof.
5-digit digital indiactor
·Built-in RFI filter and lightning arrester
Built-in local configurator with 3 push buttons
3. The transmitter can communicate using FUJI, HART,
communication protocol, and also can use FOUNDATION FIELDBUS or
PROFIBUS protocol after changing the electronic
circuit.
3:
Product Specification:
Measured fluid: Liquid,Gas,or vapour
Range, operating pressure, and overrange limit:
Type |
Operating Pressure (MPa) |
Span Limit (kPa) |
Range Limit (kPa) |
Overrange Limit (MPa) |
||
Min. | Max. | Lower | Upper | |||
FKP 01 FDP 01 |
~0.1~0.13 | 8.125 | 130 | According to the lower range limit of fill fluid | 130 | 1 |
FKP 02 FDP 02 |
~0.1~0.5 | 32.25 | 500 | 500 | 1.5 | |
FKP 03 FDP 03 |
~0.1~3 | 187.5 | 3000 | 3000 | 9 | |
FKP 04 FDP 04 |
~0.1~10 | 625 | 10000 | 10000 | 15 | |
FKP 05 FDP 05 |
~0.1~50 | 3125 | 50000 | 50000 | 75 |
Output signal: (1)FKP: DC4~20mA+HART protocol
(2)FDP: FOUNDA TION Fieldbus protocol or
PROFIBUS-PA
Power Supply: General DC10.5 ~ 45V
Intrinsic safety DC10.5 ~ 26V
With arrestor DC10.5 ~ 32V
4:
Product Parameter
Diaphragm Materials: SUS316L,Hastelloy-C
Accuracy ranting:( For spans greater than1/10 of URL ±0.1% or
±0.2%,high accuracy(Optional) ±0.065%
Output signal/ Power supply:
DC4-20mA/DC10.5~45V(Non-Explosion)
Promote/inhibit : -100%~+100%URL
Containment structure: JIS C0920 Immersion type(Equivalent IEC
IP67,NEMA6/6P
Explosion-approvals: NEPSI, FM, ATEX, IECEx, CSA,
TIIS
Ambient temperature: Sensor unit: -40~350?C / Electronics:
-40~85?C
Process connection : "1/2-14NPT, Rc1/4,
Rc1/2, 1/4-18NPT, M20×1.5"
Xi'an Tosi Da Technology Co., Ltd