TD-12/630-20C3 | |||
Main Technical Specification | |||
序号 | Parameter name | (Unit) | (Value) |
1 | Rated frequency | Hz | 50 |
2 | Rated Voltage | kV | 12 |
3 | Rated short-time(1min) power-frequency withstand voltage | kV | 48★ |
4 | Rated lightning impulse withstand voltage(Peak) | kV | 85★ |
5 | Rated Current | A | 630 |
6 | Rated short-circuit breaking current | kA | 20/25 |
7 | Rated short-circuit making current | kA | 50/63 |
8 | Rated short-time withstand current | kA | 20/25 |
9 | Rated peak withstand current | kA | 50/63 |
10 | Breakding operations of rated short circuit breaking current | Times | 30 |
11 | Circuit resistance at lowest rated contact force | μΩ | ≤25 |
12 | Rated duration of short-circuit | s | 4 |
13 | Closing force due to bellow and atmosphere | N | 80±30 |
14 | Force required to hold contacts open at full stroke | N | 100±40 |
15 | Mechanical endurance | Times | 10000 |
16 | Contacts limit erosion | mm | 3 |
17 | Storage life | years | 20 |
(Mechanical date of matching switchgear) | |||
1 | Clearance between open contacts | mm | 9±1 |
2 | Average opening speed (0~75% contact gap) | m/s | 1.1±0.2 |
3 | Average closing speed(30% contact gap-contact close position) | m/s | 0.7±0.2 |
4 | Rated added external contact final force | N | 1800±100 |
1800±100 | |||
5 | Contact bouncing duration at closing operation | ms | ≤2 |
6 | Closing and Opening non-simultaneity of three-phase contacts | ms | ≤1 |
7 | Maximum Rebound during opening | mm | ≤2 |
Meets or exceeds the electrical endurance requirements of class E2 for autoreclosing duty per IEC 62271-100 and GB1984-2014 |
|||
Note:“★”Within transformer oil or equivalent isolation medium |