Model NO. | VS1-12 | Arc-extinguishing Medium | Vacuum |
Installation | Insert | Structure | Vcb |
Poles Number | 3 | Type | Circuit Breaker |
Function | Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection), RCCB, Do as Your Request | Certification | ISO9001-2000, CE |
Rated Current | 630A/1250A/1600A/2000A/2500A | Phase Distance | 210mm/275mm |
Rated Frequency | 50/60Hz | Rated Voltage | 24kv |
Transport Package | Wooden Case | Specification | steel, expoxy resin, etc |
Trademark | LIYOND | Origin | China |
Production Capacity | 10000/Month |
Summary
ZN63A(VS1)-12 Model indoor high voltage 12kV 3 Pole High Voltage Vacuum Circuit Breaker applies to power system of rated voltage 12kv as a protective and control unit for power grid equipment and industrial power equipment It can equip with KYN28(GZS1), XGN, GG-1A and other types of switchgear panels. Related products: isolated handcart, fuse handcart and voltage transformer handcart
Structural Features:
1.This series of VCB is used Integrated design for
operating mechanism and VCB body with reasonable, beautiful
and compact arrangement.
2.This series of VCB adapted vertical insulation house
against Impact due to different weather, it can effectively
prevent VIS against damage by exterior factors.
3.The two different installation unit of Fixed type and
withdrawable type can meet the different requirements for
different switchgear.
Applying Ambient Conditions:
1.Ambient temperature:-10ºC-+40ºC
2.Relative humidity:The average humidity of a day should be
no more than 95%. The average humidity of a month should be
no more than 90%.
3.Earthquake intensity: not exceed 8 degrees.
4.Saturated vapor pressure the average pressure of a day
should be no more than 2.2kPa; the average pressure of a
month should be no more than1.8Kpa;
5.The height above sea level:≤1000 m (Except special
requirements)
6.It should be installed in the places without fire,
explosion, serious filth, and chemical erosion and violent
vibration.
No. | Name | Unit | Data | ||||||
1 | Rated voltage | kV | 12 | ||||||
2 | Rated current | A | 630 | 1000 1250 | 1600 2000 2500 3150 | ||||
3 | Rated short circuit breaking current | kA | 20 | 25 | 20 | 25 | 31.5 | 31.5 | 40 |
4 | Rated peak withstand current | kA | 50 | 63 | 50 | 63 | 80 | 80 | 100 |
5 | Rated short time withstand current | kA | 20 | 25 | 20 | 25 | 31.5 | 31.5 | 40 |
6 | Rated short circuit making current | kA | 50 | 63 | 50 | 63 | 80 | 80 | 100 |
7 | Switching operations of short circuit current | times | 50 | ||||||
8 | Rated operating sequence | O-0.3s-CO-180s-CO-180s-CO(40KA) | |||||||
9 | Mechanical endurance | times | 10000 | ||||||
10 | Rated breaking operations of the rated current | times | 20000 | ||||||
11 | Rated lighting impulse withstand voltage(full wave) | kV | 75 | ||||||
12 | 1 min. rated power frequency withstand voltage | kV | 42 | ||||||
13 | Contact stroke | mm | 9±1 | ||||||
14 | Over-travel of contacts | mm | 3.5±0.5 | ||||||
15 | Closing speed | m/s | 0.4∼0.8 | ||||||
16 | Opening speed | m/s | 0.9∼1.2 | ||||||
17 | Contact bouncing duration at closing operation | ms | ≤2 | ||||||
18 | Simultaneity of three phase closing operation | ms | ≤2 | ||||||
19 | Closing time | ms | 30∼70 | ||||||
20 | Opening time | m/s | 20∼50 | ||||||
21 | Distance between phases | mm | 150, 210, 275 | ||||||
22 | D.C component | 50% |
Note: 1. No.11&12 are provided when needed.
2. Switchgear should be with cold wind when the rated current is 4000A.
FAQ
Q: Could I have prices of your products?
A: Welcome. Please feel free to send us inquiry here. We will reply you within 24 hours.
Q: Can I get a sample before the bulk order?
A: Yes, we welcome sample order to test and check quality.Mixed samples are acceptable.
Q: Can we print our logo/ company name on products?
A: Yes, of course, we accept OEM, then need you to provide brand authorization to us
Q:Do you accept product customization?
A:Yes, of course, please provide specific drawings or parameters, we will quote you after evaluation
Q: What is the lead time?
A: The lead time depends on the quantities ordered,
generally within
7-20
days
after
receiving the
payment.
Q:
What is your Trade Terms?
A: We accept
EXW, FOB, CIF, FCA, etc.
Q: What is your payment method?
A: We accept T/T,
Western Union, Paypal,
irrevocable L/C at sight,
etc
Q: Do you inspect the finished products?
A: Yes, each step of production and finished products will be came out inspection by QC department before shipping. And we will provide goods inspection reports for your reference before shipment
Q: How to solve the quality problems after
sales?
A: Take photos of the quality problems and send to us for
our checking and confirming, we will make a satisfied
solution for you within 3 days.
Room 1801, building 2, 3 and 4, headquarters economic Park, No. 6688, Xuyang Road, Chengdong street