TeSys | |
TeSys D | |
Contactor | |
LC1D | |
Motor control Resistive load |
|
AC-3 AC-4 AC-1 |
|
3P | |
3 NO | |
Power circuit: <= 690 V AC 25…400 Hz Power circuit: <= 300 V DC |
|
80 A (at <60 °C) at <= 440 V AC AC-1 for power
circuit 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit |
|
11 kW at 400 V AC 50/60 Hz (AC-4) 18.5 kW at 220…230 V AC 50/60 Hz (AC-3) 30 kW at 380…400 V AC 50/60 Hz (AC-3) 37 kW at 500 V AC 50/60 Hz (AC-3) 37 kW at 660…690 V AC 50/60 Hz (AC-3) |
|
40 hp at 460/480 V AC 50/60 Hz for 3 phases motors 5 hp at 115 V AC 50/60 Hz for 1 phase motors 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors 20 hp at 230/240 V AC 50/60 Hz for 3 phases motors 50 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
|
DC standard | |
24 V DC | |
1 NO + 1 NC | |
6 kV conforming to IEC 60947 | |
III | |
10 A (at 60 °C) for signalling circuit 80 A (at 60 °C) for power circuit |
|
140 A AC for signalling circuit conforming to IEC
60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 1000 A at 440 V for power circuit conforming to IEC 60947 |
|
1000 A at 440 V for power circuit conforming to IEC 60947 | |
520 A 40 °C – 10 s for power circuit 900 A 40 °C – 1 s for power circuit 110 A 40 °C – 10 min for power circuit 260 A 40 °C – 1 min for power circuit 100 A – 1 s for signalling circuit 120 A – 500 ms for signalling circuit 140 A – 100 ms for signalling circuit |
|
10 A gG for signalling circuit conforming to IEC
60947-5-1 125 A gG at <= 690 V coordination type 1 for power circuit 125 A gG at <= 690 V coordination type 2 for power circuit |
|
1.5 mOhm – Ith 80 A 50 Hz for power circuit | |
Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified Power circuit: 690 V conforming to IEC 60947-4-1 |
|
0.5 Mcycles 80 A AC-1 at Ue <= 440 V 1.45 Mcycles 65 A AC-3 at Ue <= 440 V |
|
9.6 W AC-1 6.3 W AC-3 |
|
With | |
Plate Rail |
|
CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
|
GOST UL CCC CSA |
|
Control circuit: screw clamp terminals 2 cable(s) 1…2.5
mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: screw connection 1 cable(s) 1…35 mm²flexible without cable end Power circuit: screw connection 2 cable(s) 1…25 mm²flexible without cable end Power circuit: screw connection 1 cable(s) 1…35 mm²flexible with cable end Power circuit: screw connection 2 cable(s) 1…25 mm²flexible with cable end Power circuit: screw connection 1 cable(s) 1…35 mm²solid without cable end Power circuit: screw connection 2 cable(s) 1…25 mm²solid without cable end |
|
Control circuit: 1.7 N.m – on screw clamp terminals – with
screwdriver flat Ø 6 mm Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 Power circuit: 8 N.m – on EverLink BTR screw connectors – cable 25…35 mm² hexagonal screw head 4 mm Power circuit: 5 N.m – on EverLink BTR screw connectors – cable 1…25 mm² hexagonal screw head 4 mm |
|
42.5…57.5 ms closing 16…24 ms opening |
|
B10d = 1369863 cycles contactor with nominal load conforming
to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|
10 Mcycles | |
3600 cyc/h 60 °C |
Built-in bidirectional peak limiting diode suppressor | |
0.1…0.3 Uc (-40…70 °C):drop-out DC 0.75…1.25 Uc (-40…60 °C):operational DC 1…1.25 Uc (60…70 °C):operational DC |
|
34 ms | |
19 W (at 20 °C) | |
7.4 W at 20 °C | |
type mechanically linked 1 NO + 1 NC conforming to IEC
60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 |
|
25…400 Hz | |
5 mA for signalling circuit | |
17 V for signalling circuit | |
1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
|
> 10 MOhm for signalling circuit | |
M4 | |
LC1D | |
15…25 kW at 200…240 V 3 phases 30…50 kW at 380…440 V 3 phases 30…50 kW at 480…500 V 3 phases |
|
Direct on-line contactor | |
24 V DC standard |
IP20 front face conforming to IEC 60529 | |
TH conforming to IEC 60068-2-30 | |
3 | |
-40…60 °C 60…70 °C with derating |
|
-60…80 °C | |
0…3000 m | |
850 °C conforming to IEC 60695-2-1 | |
V1 conforming to UL 94 | |
Vibrations contactor open: 2 Gn, 5…300 Hz Vibrations contactor closed: 4 Gn, 5…300 Hz Shocks contactor closed: 15 Gn for 11 ms Shocks contactor open: 10 Gn for 11 ms |
|
122 mm | |
55 mm | |
120 mm | |
0.935 kg |