HZ-3120A Transformer DC Winding Resistance Tester

PortTianjin
PackagingWooden Cage
Lead Time15 days

Quick Details (View All)

nameWinding Resistance Tester

Product Details

I. Introduction

The DC resistance is the transformer’s semi-finished product, finished product test, installation, commissioning test, and electric part prevention test necessary test projectthe transformer coil can effectively find the device welding, connecting parts loose, missing unit, disconnection, and other manufacturing default and other hidden danger occurred after operation.

The DC Resistance transformer to meet fast measurement requirement, we developed HZ-3120A DC Resistance Tester. The instrument is a new powerful technology, small size, light weight, high output current and other characteristics.

The device is controlled by the microcontroller, with a high degree of automation, automatic discharge functions. It is a test instrument of high precision, simple, direct way to achieve fast transformer measurement.

II. Safety Measure

1. Before using this equipment you must carefully read the manual.

2. The equipment operator should have electric general knowledge

3. Avoid putting the equipment in the contact of the rain, corrosive gas, dust, high temperature, direct sunlight, and other places.

4. Severe vibration has to be avoiding for gauges.

5. Only an expert must maintain and adjust the equipment

6. After the test, the user must wait till the discharge alarm stopped before switching off the device, and plugging off the test cables.

7. To measure no-load regulating transformers, the user has to wait till the discharge instructions alarm stops before switching stalls.

8. During testing, do not move the testing clamp and cables

III. Technical Data

1. Output current<5mA 1A2.5A5A 10A20A

2. Resolution0.1μΩ

3. Range:  100μΩ20A

  500μΩ10A

        1mΩ5A

2mΩ8Ω   (2.5A

5mΩ20Ω (1A

10Ω20KΩ (<5mA

4. Accuracy±(0.2%+2 Readings)

5. Operating temperature0~40℃

6. Ambient humidity≤90%RH(non condensed)

7. size:400mm*225mm*350mm.

8. Instrument weight :13kg, wiring case:5kg.

Packing List

Name Qty
Main host 1
Testing line 1
Power line 1
User’s manual 1
Quality pass card 1
Insurance tube 2
Print Paper 1
Packing list 1
Grounding line 1
Serial port line 1
Test sample 1