Product Description
Main parameters:
Function:Electric leakage monitor, AC measurement, phase wire
identification
Range:0.1mA-400A(below 42-60HZ. AC380V)
Resolution ratio:100uA
Test accuracy:0.1mA-10mA:±3%+5dgt.
11mA-300A:±2%+5dgt
Range switch:Automation
Phase wire measurements:Non-contact type
Data transfer method:USB/GPRS
Data storage capacity:Built-in 128M&Micro-Sd card, at
least store data for 30 days
Data consultancy:Device terminal, APP client, PC
terminal
Basic function:
(1)Leakage alarm:
Users can set alarm threshold, give sound & light warning and
initiatively upload alarm information to APP client when
detected that leakage current over the threshold.
(2)Leakage data log:
When open log function, can save the measured leakage current
and occurred time into built-in D card and can view
historical leakage current data through APP client or
computer after imported.
(3)APP remote monitoring and operation:
One APP client can manage up to decades & hundreds pieces
devices and the users can operate the devices through APP,
such as set alarm threshold, view historical data and receive
leakage alarm information etc.
(4)Non-contact type phase wire identification:
Identify phase wire by adopting method of CT couple, no need
to contact directly with power line to prove personal
security.
(5)Analysis on upper computer software:
Import the data from device to computer and use companion
analysis software draw intuitive leakage current picture of
(current)-time which makes the result be clear at a
glance.