The solid insulated ring main unit adopts armored metal
enclosed structure:
-The cabinet is made of aluminum coated zinc plate, which is
processed and assembled by numerical control punch and numerical
control bending.
The cabinet has the characteristics of compact structure, high
precision and strong corrosion resistance.The protecction level
reaches IP41.
-The switch compartment is of one-piece structure, covered with
epoxy resin. The interior of the switch is not affected by the
external environment, and the protection level reaches IP67
Application environment:
-Ambient temperature -25°C ~ +45°C
-Altitude: ≤ 4,000m (If >1,000m Special remarks are
required)
-Seismic fortification intensity:8
-Indoor or outdoor installation
-It shall not be installed in indoor with corrosive, flammable,
explosive and other dangerous things in the surrounding air, and
places with violent vibration around.
Specification:
Description
|
Unit
|
Load
switch unit
|
Circuit
breaker unit
|
Rated
voltage
|
kV
|
12
|
12
|
Rated
frequency
|
Hz
|
50
|
50
|
Rated
current
|
A
|
630
|
630
|
Power-frequency
withstand voltage
|
kV
|
42/48
|
42/48
|
Lightning
impulse withstand voltage
|
kV
|
75/85
|
75/85
|
Rated short
circuit breaking current
|
kA
|
-
|
20
|
Rated
short-time withstand current
|
kA
|
20
|
20
|
Rated
duration of short-circuit
|
S
|
4
|
4
|
Rated peak
withstand current
|
kA
|
50
|
50
|
Rated short
circuit closing current
|
kA
|
50
|
50
|
Loop
resistance
|
μΩ
|
≤150
|
≤150
|
IP
class(Pole)
|
|
IP67
|
IP
class(Cabinet)
|
|
IP4X
|
The phase
distance between poles
|
mm
|
Busbar
compartment140 Cable
compartment120
|
Dimention(L*W*H)
|
mm
|
440*850*1830
|
For more details, pls contact us.