Hallo,
I wish to purchase a water chiller with the following specifications for purposes of utilization in a fruit processing plant :
Technical Specifications :
Refrigerant : R404 or any other approved type(non-ozone depleting types).
Inlet process water temp : 75c (167F).
Required chilled water temp : 15c(59F)
Required temp.delta : 75c-15c=60c
Required chilled water flow rate : 4.5m3/hr(990UK gallons/hr)
Required chilled water pressure : 4 bar
Sizing
Temperature differential=167-59=108F.
BTU/hr calculation
BTU/hr=Gallons per hr x 8.33 x temperature differential
BTU/hr=990 x 8.33 x 108
BTU/hr=890,643
3.Calculation of tons of cooling required
Tons=BTU/hr/12,000
=890,643/12,000
=74.2 tons of cooling
4.Oversize by 20%
Ideal size=1.2 x x tons of cooling
=1.2 x 74.2
=89 tons of cooling
Kind regards,
Mark Kinyua,
Operations Director
Kifaru Corporation Ltd.
Have you found what you were looking for? No? Post Your requirements for FREE!
Want to sell products to global buyers? Post Your Products Now! for Free.