15KV SF6 Gas Load Break Switch

FOB Price 2300 - 6000 USD / USD
MOQ5 Pcs
PackagingWooden case
Lead Time25-45days

Product Details

15 kv pole mounted disconnect switch is suitable for rated voltage 15kV, rated current 630A, 50/60Hz distribution network breaking. The load current or overload current in a power system automatically isolates the faulty sections of the distribution line.

With the latest technology electronic controller, this manual load break switch realizes manual operation, electric operation, and remote operation. The electronic controller is installed in the stainless steel box and can be used under various climatic conditions. In addition, 15kv load break switch cable and wireless modems can be installed in the box to realize remote monitoring and control. Simple installation and arrangement on the pole are convenient, quick, and low construction cost.

Characteristics of 15KV SF6 Load Breaker Switch

The 15KV pole mounted disconnect switch is made of proven durable, corrosion-resistant material. (304L stainless steel plate for warships), ensure a long service life (30years), our 15kv load break switch can carry out a series of operations, with the pole top equipment ideal characteristics.

Each GOPOWER 15kv load break switch has been filled with sf6 gas before leaving the factory, sealed treatment. The 15 kv pole mounted disconnect switch test was carried out according to IEC60265-1 (1988) GB 3804-1990 standard.

SF6 Gas 15KV Load Break Switch In Pole Mounted Switch Solution

15kv load break switch has a certain interrupting capacity because of the interrupting device, but 15 kv pole mounted disconnect switch is not as strong as the interrupting capacity of the circuit breaker, which can split the normal working current, and in the case of short circuit, he can only silently withstand the short circuit current, and if this time the manual or electric breaking may explode, so the load switch is generally used together with the current limiting fuse (load switch + fuse is not the standard configuration, and can also be used without fuse) In the event of an overload or short circuit, the circuit is broken by a fuse. In order to save costs, the load switch + fuse can replace the circuit breaker. Inquiry more pole mounted switch solutions

Specification of 15 KV Pole Mounted Disconnect Switch

Products Type

FWX-15

Basic Ratings

Maximum System Voltage

15KV

Rated Continuous Current

630A

Rated Frequency

50/60Hz

Short Time Withstand Current

IKA/sec

Making and Breaking Capacity

Mainly Active LoadCurrent

630A

Number of Load-break Operations

400times

Short-circuit Making Current(peak)

50KA

Number of Making Operations on 15 KV Pole Mounted Disconnect Switch

Number of Making Operations

5 times

Cable Charging Current

lOA

Line Charging Current

lOA

Closed Loop Circuit Current

630A

Transformer Magnetizing Current

22A

Power Frequency Withstand Current Test

Wet Condition- 10 sec (Ph- Ph-Eth, Across Interrupters)

50KV

DryCondition- I min ( Phase to Phase, Phase to Earth)

50KV

Dry Condition - 1 min (Across Interrupter )

60KV

Impulse Withstand Current Test(1.2 x 50 µs)

Internal Arc Test of 15 KV Pole Mounted Disconnect Switch

Internal Arc Test

20kA /0.1 sec

Arc Extinction Medium

SF6 Gas

Insulation Medium

SF6 Gas

Creepage Distance (Porcelain)

560mm

IP Level

54

Operation Performance

Closing/Opening Tin

< O. l sec

Mechanica l Operations (Guaranteed)

l OOOO times

Operating Temperature.1re(*Manual Type)

-25+70℃

Gas Pressure

Nominal Pressure (kg/cm2 G, at 20°C)

0.07

Bursting Pressure (kg/cm2 G)

4 ~ 6

Minimum Gas Pressure (kg/cm2 G)

0.0

Leakage Rate (cc/ sec)

1%

Other Ratings & Specifications of 15 KV Pole Mounted Disconnect Switch

Other Ratings & Specifications

Internal Arc Test

20kA /0.1 sec

20kA /0.1 sec

20kA /0.1 sec

Arc Extinction Medium

SF6 Gas

SF6 Gas

SF6 Gas

Insulation Medium

SF6 Gas

SF6 Gas

SF6 Gas

Creepage Distance (Porcelain)

380mm

700mm

1055mm

Creepage Distance (Silicon)

780mm

1200mm

1550mm

Dry arcing distance

≥200mm

IP Level

65

65

65

Operation Performance

Closing/Opening Time

1sec

1sec

1sec

Mechanical Operations (Guaranteed)

10000times

10000times

10000times

Operating Temperature (*Manual Type)

-25+70℃

-25+70℃

-25+70℃

Gas Pressure

Nominal Pressure (MPa, at 20°C)

0.07

0.07

0.07

Bursting Pressure (MPa)

0.40.6

0.40.6

0.40.6

Minimum Gas Pressure (MPa)

0.05

0.05

0.05

Leakage Rate (cc/ sec)

≤0.5%

≤0.5%

≤0.5%

Voltage sensors

CT ABC 10P10 5VA

400:5

400:5

400:5

Incoming side and outgoing side of the voltage sensor

6 Voltage sensorbuilt-in Phase voltage:(2436kV/√3/3.25V/√3

Special attention should be paid to the voltage sensor, which must be directly fed by the 15kv load break pole mounted disconnect switch. No additional adjustment circuit can be added to the controller. The voltage signal of the switch into the test line needs to be tested separately.

Zhuhai Gopower Smart Grid Co., Ltd. was founded in 1998. Gopower's products are manufactured in accordance with the international standards IEC61970, IEC61968, and IEC61850.

Zhuhai Gopower Smart Grid Co., LTD

Building 3,No. 2007 Mingzhu South Rd ,Qianshan,Zhuhai,Guangdong,China

China

Get Free Quotes From Multiple Sellers

Register Your Company