Performance Data
System Voltage
Rated Voltage (kV):0.1-275
Nominal discharge current (kA)
High current capability (4/10us) kA
Energy Class :
Energy absorption Capability kJ/kV
Short Circuit (Pressure relief) kA:40
Standard in accordance with:IEC60099-4
Porcelain housed for outdoor
application
For protection of transformer & switchgear.
Highly non-linear MOV.
Explosion Proof - Pressure Relief Design.
High energy handling capacity.
Glazed brown Porcelain Housing.
Corrosion proof Aluminum alloy metal flange.
Suitable for Ambient -400C to +550C.
manufactures effective surge protection device with the
modern technology of highly non-linear Zinc
Oxide Varistor blocks and thus diverts natural lightning
surge and switching surge to earth and simultaneously
clip off
any follow on current. Our station class arresters are
designed to provide maximum safety to personnel and
sub-station
equipment even at the enormous short circuit duty.
Research and Development is an ongoing process at
Elektrolites
with the active collaboration of experts in the
industry.
CONSTRUCTION & OPERATING
PRINCIPLE
Lightning
Arrestors
11
kV
No.
|
DETAIL
|
UNITS
|
DATA
|
|
Type
|
|
11kV gapless type metal oxide surge
arrester - Distribution class
|
1.
|
Nominal system voltage
|
kV
|
11
|
2.
|
Highest system voltage
|
kV
|
12
|
3.
|
Basic Insulation Level (BIL)
|
kV
|
95
|
|
3. Ratings and type of surge
arrester
|
|
|
4.
|
Specification to which surge arrester
complies
|
|
IEC
60099-4
|
5.
|
Rated voltage of surge arrester
|
kV
|
10
|
6.
|
Nominal, 8/20 µs, discharge current rating
of
surge arrester
|
kA
|
10
|
7.
|
Maximum continuous operating voltage of
surge arrester
|
kV
|
7.3
|
8.
|
Gapless or gapped type metal-oxide surge
arrester
|
|
Gapless
|
9.
|
Material of insulation
|
|
High temperature vulcanised silicon
rubber
|
10.
|
Rated frequency of surge arrester
|
Hz
|
50
|
11.
|
Design altitude of surge arrester (above sea
level)
|
m
|
1 400m
|
12.
|
Design ambient temperature of surgearrester
|
oC
|
-1 to40
|
13.
|
Specific creepage distance of surge arrester
|
.mm/kV
|
25
|
|
Automatic earth lead
disconnectors
requirements
|
|
|
14.
|
Automatic earth lead disconnectors to be
fitted
|
Yes/No
|
YES
|